GGD 3AA Series Low-Voltage Fixed Distribution Cabinet

  • 1. Reliable Power Distribution Performance
    Suitable for AC 50/60Hz, 400V-690V systems with main busbar rated current 400A-1600A. Complies with GB7251.1 and IEC61439 standards, ensuring stable power distribution, control, and protection for industrial, commercial, and public facilities.
  • 2. Safe & Durable Design
    Features fully enclosed metal structure with anti-misoperation devices and IP30 protection grade (upgradable to IP40), adapting to complex environments like dusty or moderately humid areas. 100% pre-delivery testing and CCC/CE certifications guarantee safety.
  • 3. Cost-Effective & Flexible
    Economical for small-to-medium projects with customizable size, switch brands, and circuit counts. Standardized design enables quick on-site installation, while modular structure supports later upgrades (e.g., remote monitoring, energy metering).
  • 4. Wide Application Range
    Ideal for power distribution in factories, malls, schools, hospitals, residential communities, and agricultural facilities. Meets both basic power control needs and extended functions like temperature-humidity monitoring or fault indication.
  • 5. Assured After-Sales & Delivery
    Comes with 12-month warranty, 7×24 technical support, and installation guidance. Standard configurations ship in 15-20 workdays; includes test reports and schematics. Supports bulk OEM/ODM customization.

📌 Product Name

GGD Series Low-Voltage Fixed Distribution Cabinet (Indoor Type)

📝 Product Overview

The GGD type low-voltage fixed distribution cabinet is an economical and practical low-voltage switchgear. The rated current of the main busbar ranges from 400A to 1600A, suitable for power distribution systems with AC 50(60)Hz and rated working voltage of 400V to 690V. Adopting a fixed installation method, this product is widely used in power distribution, power control, and lighting distribution in various industrial and mining enterprises, commercial buildings, and infrastructure, for power distribution, control, protection, and monitoring.

With advanced design and modular structure, it complies with international standards such as GB7251.1 and IEC61439, featuring high safety, good maintainability, and intelligent expansion capabilities.

⚙️ Product Features

  • Simple Structure: Fixed installation, compact structure, easy operation and maintenance
  • Economical and Practical: High cost performance, suitable for small and medium-sized distribution projects
  • Safe and Reliable: Fully enclosed metal structure with anti-misoperation and isolation devices; protection grade up to IP30, adapting to complex environments
  • Flexible Configuration: Supports personalized customization of size, color, switch brand, and number of circuits
  • Easy Installation: Standardized design for simple and quick on-site installation
  • Strong Expandability: Can integrate modules such as remote monitoring, electric energy metering, and temperature and humidity monitoring, supporting later capacity expansion and function upgrading
  • Compliant with Multiple Certifications: CCC, CE, ISO9001; 100% inspection before delivery

🏭 Application Fields

  • Industrial Field: Power distribution rooms of small and medium-sized factories
  • Commercial Places: Power distribution in shopping malls and supermarkets
  • Public Facilities: Power distribution systems in schools and hospitals
  • Infrastructure: Community distribution rooms and pump room control
  • Agricultural Production: Power distribution control for agricultural processing equipment

Main Structural Components

Component Function Description
Cabinet Frame Assembled with high-quality cold-rolled steel plates, divided into busbar room, electrical component room, and cable room
Main Busbar System Horizontal busbar (400A-1600A) with optional copper bar specifications
Functional Units Fixed-installed electrical components such as circuit breakers, contactors, and fuses
Protection System Functions such as overload and short-circuit protection
Instrument Monitoring Optional voltmeters, ammeters, energy meters, etc.
Incoming and Outgoing Line System Optional bottom or top incoming/outgoing line methods

📐 Technical Parameters

Item Parameter Range
Rated Working Voltage AC400V (max. 690V)
Rated Insulation Voltage AC690V
Rated Frequency 50/60Hz
Rated Current of Main Busbar 400A/630A/800A/1000A/1250A/1600A
Rated Short-Time Withstand Current 15kA/1s (main busbar)
Rated Peak Withstand Current 30kA
Protection Grade IP30/IP40
Cabinet Material Cold-rolled steel plate/stainless steel plate/galvanized steel plate (optional)
Cabinet Size Width 600 (800/1000) mm × Depth 600 (800) mm × Height 2200 mm
Operating Ambient Temperature -5℃~+45℃ (extreme -15℃)
Relative Humidity ≤95% (+25℃, no condensation)
Altitude Requirement ≤2000m
Executive Standards – GB/T 7251.2-2023 “Low-Voltage Switchgear and Controlgear Assemblies”
– GB/T 15576-2020 “Low-Voltage Reactive Power Compensation Devices”
– IEC 61439-1:2020 Low-Voltage Switchgear Standards

🔌 Optional Configurations and Expansion Modules

  • Smart electric meter / power quality analysis module
  • RS485 communication interface (Modbus protocol)
  • PLC controller, touch screen intelligent monitoring system
  • UPS or diesel generator linkage interface
  • Temperature and humidity sensor, heating and dehumidification device
  • Leakage monitoring, fault indicator

📦 Packaging and Delivery

  • 100% electrical performance testing before leaving the factory
  • Provide installation instructions, electrical schematics, and qualification certificates
  • Standard wooden box packaging, suitable for long-distance transportation
  • Delivery cycle: 15~20 working days for standard configuration; please inquire separately for customized products

🛠️ Installation and After-Sales Service

  • Attached with installation guide, supporting remote video or on-site technical guidance
  • Warranty period: 12 months
  • Service method: Provide 7×24-hour technical support, support regular inspection and parts replacement
  • Support OEM/ODM mass customization

8. Selection Suggestions and Precautions

  1. Current Rating Selection:
    • Select the main busbar current according to 1.2 times the actual load
    • Consider the development margin for the next 5 years
  2. Protection Configuration:
    • It is recommended to configure frame circuit breakers for important circuits
    • Molded case circuit breakers can be used for general circuits
  3. Installation Environment:
    • Anti-condensation measures are recommended for humid environments
    • Protection upgrade should be considered for dusty environments
  4. Special Requirements:
    • A compensation cabinet can be added when there is a need for reactive power compensation
    • Dual power supply switching is recommended for important loads
  5. Space Consideration:
    • Confirm the size limit of the installation site
    • Consider the space required for maintenance and operation

Note: This product can be configured with components from mainstream domestic brands (such as Chint, Delixi, Changshu Switch, etc.), providing multiple cost-effective solutions. It is recommended to provide a detailed load list and system diagram to recommend the optimal configuration. For special application requirements, customized design solutions can be provided.